8-11
Example of an aborted (incompatible device problem) test
-----------------------------------------------------------------
Service Port Page 1
Report 6: TrueAlert Device Status Report 10:23:45am WED 07-FEB-07
TPS 3
SLC 1
POINT ID CUSTOM LABEL TEST RESULT
--------- --------------------------------- --------------------
T3-1-1 Auditorium North PASSED
T3-1-2 Auditorium South PASSED
T3-1-3 Auditorium Lobby DEVICE NOT COMPATIBLE
NOMINAL CURRENT (A): 0.80
WORST_CASE CURRENT (A): 1.17
WORST_CASE VOLTAGE ABOVE/BELOW THRESHOLD (V): 1.2
SLC HAS NOT PASSED UNLESS ALL DEVICES ARE MARKED AS PASSED
-----------------------------------------------------------------