3.4 Safety
In the interest of safety, the load bank is equipped with an automac system to de-
energize all the load if condions are met that may be dangerous to the operator or
could damage the hardware. If the load elements aren’t cooled properly due to a fan
failure or high exhaust temperature, the load bank will de-energize any applied load.
Aer operaon, the load bank has an auto cool down feature to prevent burns and
injury during transportaon aer use.
3.5 Specicaons
The table below shows the operaon KW at the various voltages across the Powerstar
and the dierent model of Northstar Load Banks.
Model KW Rang 600VAC, 3Ph 480VAC, 3Ph 240VAC, 3Ph 240VAC, 1Ph 230VAC, 1Ph 208VAC, 2Ph 208VAC, 1Ph
PowerStar 110
110 480VAC, 3Ph
110KW/132A 110KW/264A 70.4KW/293A 64.7KW/281A 82.5KW/229A 52.9KW/254A
NorthStar 125 125 208VAC, 3Ph
125KW/345A 80KW/385A
NorthStar 150 150 600VAC, 3Ph
150KW/145A 96KW/115A 24KW/58A
Table 1 Specications of Load Banks