6.3 Handling
6.3.1 General Handling Informaon
When moving the Load Bank, please keep the device upright and do not transport
on its side. Use the aached rollers for short distances. If the unit needs to be
lied, only li the unit using the handles on the sides or liing the from the
boom of the unit. Avoid liing from the Cam-Lok connecons as it will apply
extra pressure to the BUS connectors. Do not insert any liing tools in the fan
grang. Avoid impact while transporng as well as avoid dropping the unit in
general. While the metal casing is quite strong, avoid dropping anything heavy on
the unit.
6.3.2 Aer-Operaon Handling Informaon
Because of the nature of the Load Bank’s operaon, the unit will be extremely
hot. To prevent burn injury, allow the fans to run for a few minutes without an
applied load at the end of operaon. When the unit has cooled, turn the fans o
and move it as necessary.
6.4 Basic Operaons
6.4.1 Powering the Load Bank
2. Before starng the Load Bank, ensure that the load bank is connected
to an independent ground line.
3. Connect the Control Power Cable to the control power outlet, connect
the HMI(Port 3) to the “In” port (Port 1), and connect the cables from
the load source to the Cam-Lok connectors.
4. Plug in the Control Power Cable into a 120V, 15A maximum external
receptacle.
5. Visually observe for any possible fan obstrucon.
6. The HMI hand-held controller will energize. On the HMI hand-held
controller, press the “On” switch for the “Fan.” (See Figure 4). The
fans will start.
Figure 4 Home Screen; No Power