7.0 ALARMS AND WARNINGS
7.1 Introducon
With Simplex Portable Load Banks, there are few things that will cause a serious issue.
One of the primary alarms that will occur is an over-temperature alarm.
In this secon, you will learn:
What triggers an alarm.
How to reset the unit.
7.2 Over-temperature Alarm
When the exhaust temperature exceeds 235° F (~112° C). The load bank will open
all contactors, this removes the load and allows the load bank to cool to an operable
temperature. Once cooled, fully cycle the units power and try to complete tesng.
When powering the unit off, leave it off for a couple of seconds before powering
the unit. If the problem persists, please call 1-800-637-8603.