CAUTION
This load bank is high-powered, technical, industrial equipment operang at dangerous
voltages, and temperatures. It is capable of damage to itself or property or personnel,
if improperly used. It is not a consumer product. It must be installed, connected, and
operated by personnel properly trained and experienced in its use. An operator’s
manual is supplied with each load bank. It is imperave that the operator be familiar
with its contents and has access to it during operaon.
The following cauons should be observed before and during operaon:
1. Check all aspects of the load bank (intake/exhaust screen, louvers, fans, and load
elements) for foreign objects.
2. Posion and install load bank with great consideraon given to large cubic airow
requirements, exhaust temperature and velocity. The exhaust temperature of a
large load bank rapidly diminishes downstream but can easily exceed 300°F within
20 feet of exhaust outlet. Therefore, do not point exhaust at any nearby surface or
object, which may be adversely aected by high temperature. This includes but is
not limited to painted surfaces, tar paper and asphalt roofs, water sprinkler heads,
re alarms, and volale material.
Do not use in conned spaces with less than a 4-foot clearance for intake air and
less than a 20-foot clearance for exit of high temperature exhaust. Do not permit
vercal airow unit with wheels to sink into so surfaces thereby cung o boom
air intake. Be concerned with possibility that the load bank may have to compete
with cooling air requirements of a nearby running engine generator set where cool-
ing air intake to a conned space may not be adequate for both engine and load
bank. Be especially careful not to bounce hot exhaust air o nearby obstrucons for
re-circulaon through the load bank.
3. Verify that all control switch posions are correct for intended usage before making
connecon.
4. The load cables carry high amperage. Be constantly aware of possibility of
inducvely heang adjacent ferrous objects to temperatures sucient to damage
cable insulaon.
5. If load bank does not have a fan reversal switch, give extra aenon to proper
phasing of power cable and external control power connecon to assure proper fan
rotaon.
6. Always connect safety ground cable to a proper ground. Do not rely on a possible
grounded neutral somewhere else in the system.
7. Do not let equipment operate unaended for long periods of me.
8. Do not store or operate in rain or spray unless unit is designed for this service or
adequate protecon is provided.
9. Rounely inspect all components and electrical connecons for ghtness and
integrity.
10. Repair any damaged or degraded components and wiring without delay.