51
Installation and Maintenance
Step
Procedure
b
Remove screw xing the water bae (xing pipe);
remove screws xing the tube clip, then remove the
water bae(xing pipe).
8. Remove Capillary Sub-assy
Cut the cable tie and remove the xed block of tube.
Unsolder the welding joint between the capillary
subassy
and then remove the capillary sub-assy.
Note:
1.Before unsoldering the welding joint, please make
sure the refrigerant is discharged completely.
2.Before unsoldering the welding joint of capillary,
wrap the capillary with a wet cloth completely to avoid
damage to the capillary caused by high temperature.
Seal the discharge pipe port and suction pipe port of
compressor with rubber plug or rubber paper to avoid
impurities getting into the pipe.
9. Remove 4-way valve assy
Unsolder the welding joint connecting the 4-way valve
assy and then unsolder the 4-way valve assy.
Note:
1.Before unsoldering the welding joint, please make
sure the refrigerant is discharged completely.
2.Before unsoldering the welding joint connecting the
4-way valve, wrap the 4-way valve assy with a wet cloth
completely to avoid damage to the valve caused by high
temperature.
Tube Clip
4-way valve assy
Capillary Sub-
assy
Junction
Welding joint
Welding joint
screws
screws