When parameters have been changed as required, press the left key (A) again
until the display digit shows SP (Save parameters). Press any of the other
keys (B or C) to save all the parameters into the EEPROM.
NOTE: Change all the required parameters before saving them. If you decide
not to save the parameters you have changed, push the left key (A) again.
PARAMETER CHANGE TABLE
PARAMETER
DISPLAY
LEFT NUMBER
RANGE
KEY
EFFECT
KEY B
KEY EFFECT
KEY C
FACTORY
DEFAULT
Relay 1
threshold
1
1…99%
add 10%
add 1%
5%
Relay 2 threshold
2
1…99%
add 10%
add 1%
60%
4 mA adjustment
3
-
increase
current
decrease
current
set to 4 mA
20 mA
adjustment
4
-
increase
current
decrease
current
set to 20 mA
Alarm delay time
5
0…180s
add 10s
-
0
Analog output
filter
time constant
6
0…300s
add 10s
-
0
Percent level of
full range during
autosetup
7
10-50 %
increase 10
%
decrease 10 %
20 %
Reference check
interval
8
0-99 hour
increase
decrease
0
Reference check
alarm setup
9
0-8min or
continuous
increase
decrease
0
Output scale
0.
1-100 %
increase
decrease
20 %
Output zero point
adjustment
10.
1-99 %
increase
decrease
0 %
*PIN
code/Manual
Range( S304)
1.
000-999
increase
decrease
1.1.1 (S305)
Save parameters
- SP
save all
Save all
*) If you have the model 304, please see also the chapter about the manual range set up
option.
Table 2. Parameter change table