AC Output
STP8000TL-20 STP9000TL-20 STP10000TL-20
Rated power at 230V, 50Hz 8000W 9000W 10000W
Maximum apparent AC power at
cosφ=1
8000VA 9000VA 10000VA
Rated grid voltage ∼3/N/PE,
230V / 400V
∼3/N/PE,
230V / 400V
∼3/N/PE,
230V / 400V
AC voltage range* 160V to 280V 160V to 280V 160V to 280V
Nominal AC current at 220V 11.6A 13.1A 14.5A
Nominal AC current at 230V 11.6A 13.1A 14.5A
Nominal AC current at 240V 11.1A 12.5A 13.9A
Maximum output current 11.6A 13.1A 14.5A
Total harmonic distortion of the output
current with total harmonic distortion
of the AC voltage <2%, and AC
power >50% of the rated power
≤3% ≤3% ≤3%
Maximum output current under fault
conditions
20A 22A 25A
Rated power frequency 50Hz 50Hz 50Hz
AC power frequency* 50Hz / 60Hz 50Hz / 60Hz 50Hz / 60Hz
Operating range at AC power fre-
quency 50Hz
45.5Hz to
54.5Hz
45.5Hz to
54.5Hz
45.5Hz to
54.5Hz
Operating range at AC power fre-
quency 60Hz
55.5Hz to
64.5Hz
55.5Hz to
64.5Hz
55.5Hz to
64.5Hz
Displacement power factor cosφ, ad-
justable
0.8underexcited
to 1 to
0.8overexcited
0.8underexcited
to 1 to
0.8overexcited
0.8underexcited
to 1 to
0.8overexcited
Feed-in phases 3 3 3
Phase connection 3 3 3
Overvoltage category in accordance
with IEC60664-1
III III III
* depending on the configured country data set
11Technical Data
SMA Solar Technology AG
Operating ManualSTP5-12TL-20-BE-en-1562