Operating Manual
SUNNY TRIPOWER
5000TL/6000TL/7000TL/8000TL/9000TL/
10000TL/12000TL
STP5-12TL-20-BE-en-15 | Version 1.5ENGLISH

Table of Contents

Questions and Answers

  • M
    Marie JordanSep 23, 2025
    What to do if SMA Inverter shows EEPROM dBh error?
    • B
      Bonnie FarmerSep 23, 2025
      If your SMA Inverter displays 'EEPROM dBh', the EEPROM data is defective, and the inverter has shut down because the data loss has disabled important functions. Contact the SMA Serviceline.
  • S
    Steven DrakeAug 25, 2025
    How to fix SMA 5000TL showing 'Check L-N-PE'?
    • B
      Barbara OconnorAug 25, 2025
      If your SMA Inverter displays 'Check L-N-PE', it means L and N are swapped on the AC connection or PE is not connected. Make sure that the AC cable is correctly connected.
  • J
    Jason MillerAug 25, 2025
    Why is my SMA 5000TL derating?
    • V
      Victoria OrtegaAug 26, 2025
      The SMA Inverter might be derating (reducing its power output) due to overheating. In this case, clean the fans. Alternatively, derating can occur if the DC input current exceeds the inverter's maximum input current; ensure that the PV plant is designed correctly.
  • A
    adammooreAug 27, 2025
    What does ACVtgRPro mean on my SMA 5000TL?
    • A
      Abigail HicksAug 27, 2025
      If your SMA Inverter displays 'ACVtgRPro', the ten-minute average mains voltage is no longer within the permissible range. Check that the mains voltage at the termination point of the inverter is permanently in the permissible range. If the mains voltage is 253 V or higher, contact the network operator.
  • R
    Ralph RodriguezAug 27, 2025
    What does 'Earthfault' mean on my SMA 5000TL and how to fix it?
    • M
      Michaela RobbinsAug 27, 2025
      If your SMA Inverter displays 'Earthfault', it indicates that the electrical insulation between the PV plant and earth is defective. Make sure that the PV plant is insulated correctly.
  • D
    David FinleySep 14, 2025
    How to solve Check L-N-PE error on SMA 5000TL Inverter?
    • E
      elewisSep 14, 2025
      The 'Check L-N-PE' error on your SMA Inverter indicates that the L and N are swapped at the AC connection or PE is not connected. Check the AC connection.
  • A
    alecthomasSep 12, 2025
    What does SD-DI-Wandler error mean on SMA 5000TL Inverter?
    • U
      urobertsSep 12, 2025
      The 'SD-DI-Wandler' error on your SMA Inverter indicates an insulation fault on the DC side. Check the plant insulation and inspect for ground faults.
  • X
    xruizSep 13, 2025
    What does Imax mean on SMA 5000TL?
    • F
      fmorenoSep 13, 2025
      The 'Imax' message on your SMA Inverter indicates overcurrent on the AC side, meaning the current in the AC grid is higher than specified. Check the system design and grid conditions.
  • C
    Christine GardnerSep 5, 2025
    How to fix PV overvoltage on SMA 5000TL Inverter?
    • D
      David DonaldsonSep 5, 2025
      If your SMA Inverter displays 'PV-Overvoltage' and instructs you to disconnect DC, it indicates an overvoltage at the DC input, which can damage the inverter. Immediately disconnect the inverter from the grid by: 1. Turning off the line circuit breaker. 2. Removing the Electronic Solar Switch. 3. Disconnecting all the DC plug connectors. Then, check the DC voltage. If it exceeds the maximum input voltage, inspect the plant design or contact the PV generator installer. If the voltage is within the limit, reconnect the inverter. If the message reappears, disconnect the inverter and contact the SMA Serviceline.
  • B
    Brittany ThompsonSep 2, 2025
    What causes damage to the SMA 5000TL due to moisture and dust intrusion?
    • D
      Dale BrownSep 2, 2025
      Damage to the SMA Inverter from moisture and dust intrusion can occur if the ESS is not plugged in or incorrectly plugged in during operation. Always plug in the ESS until it is flush with the enclosure and ensure that the gap between the ESS and the enclosure is no more than 1 mm.

SMA 5000TL Specifications

General IconGeneral
Nominal AC power5000 W
TopologyTransformerless
Nominal AC voltage230 V
Number of MPP trackers2
Operating Temperature Range-25 °C to +60 °C
CoolingConvection
Protection DegreeIP65
AC voltage range180 V - 280 V