11 Troubleshooting
SMA Solar Technology AG
Operating manualSTP50-4x-BE-en-23106
Event number Message, cause and corrective measures
9005
Changing of grid parameters not possible > Ensure DC supply
This error can have the following causes:
The parameters to be changed are protected.
The DC voltage at the DC input is not sufficient to run the main CPU.
Corrective measures:
Enter the SMA Grid Guard code.
Ensure that at least the DC start voltage is available (green LED is
flashing, pulsing or glowing).
9007
Abort self-test
The self-test (Italy only) was terminated.
Corrective measures:
Ensure that the AC connection is correct.
Restart the self-test.
9033
Rapid Shutdown was triggered
The inverter detected the triggering of a Rapid Shutdown. The AC side of the
inverter was disconnected.
9034
Error in Rapid Shutdown System
This message can have the following causes:
The Rapid Shutdown Function was not correctly configured.
The PV array could not be correctly disconnected. Voltage can be
applied to the DC inputs of the inverter.
The standby voltage of all PV array disconnect switches of a string is >
30V.
Corrective measures:
Check the configuration of the Rapid Shutdown function and ensure that
the operating mode selected is selected according to the DC
disconnection unit used.
Check the functionality of the PV array disconnect switches.
Check the standby voltage of the PV array disconnect switches used and
ensure that the standby voltage of all PV array disconnect switches of a
string < 30V.