SMA Solar Technology AG 5 Technical Data
Installation Guide SHP75-10-STP60-10-IA-xx-18 41
5 Technical Data
5.1 Specifications
Parameter SHP 75-10 STP 60-10
AC
Nominal apparent power
1)
75000 VA 60000 VA
Nominal active power
2)
75000 W 60000 W
Reactive power range
1)
0 to 75000 var 0 to 60000 var
Nominal AC voltage 3 / grounding conductor;
400 V (50 Hz)
3 / grounding conductor;
400 V (50 Hz)
Supported grounding systems TT, TN TT, TN
Nominal AC current 3 x 109 A 3 x 87 A
Max. AC current 3 x 109 A (at 400 Vac) 3 x 87 A (at 400 Vac)
AC total harmonic distortion
(THD at nominal output power)
< 3% < 3%
Power factor – standard > 0.99 at nominal power > 0.99 at nominal power
Displacement power factor 0 overexcited to 0 underexcited 0 overexcited to 0 underexcited
Stand-by power consumption
(for communication)
< 3 W < 3 W
Nominal grid frequency (range) 50 Hz/60 Hz (± 10%) 50 Hz/60 Hz (± 10%)
DC
Max. PV array power 112500 W 90000 W
Input voltage range
(at 400 Vac / at 480 Vac)
565 V to 1000 V / 680 V to 1000 V 565 V to 1000 V / 680 V to 1000 V
Nominal voltage DC
(at 400 Vac / at 480 Vac)
630 V / 710 V 630 V / 710 V
MPP voltage range
(at 400 Vac / at 480 Vac)
570 V to 800 V / 685 V to 800 V 570 V to 800 V / 685 V to 800 V
Startup voltage
(at 400 Vac / at 480 Vac)
600 V / 720 V 600 V / 720 V
Max. input voltage 1,000 V 1,000 V
Min. power on the grid 100 W 100 W
Max. input current / max.
short-circuit current
140 A / 210 A 110 A / 150A
Number of independent MPP inputs
/ strings per MPP input
1/1 (split up by external PV array
junction box)
1/1 (split up by external PV array
junction box)
Surge categories AC: Surge category III
(SC III),
PV: Surge category II (SC II)
AC: Surge category III
(SC III),
PV: Surge category II (SC II)