SMA Solar Technology AG 5 Mounting
Installation Manual SB30-50TL-21-IA-en-21 27
Observe the recommended clearances to walls,
other inverters or objects as depicted in the
diagram to ensure adequate heat dissipation and
to give you sufficient room to remove the ESS, if
necessary.
Multiple inverters installed in areas with high ambient temperatures
There must be sufficient clearance between the individual inverters to ensure that the cooling
air of the adjacent inverter is not drawn in.
If necessary, increase the clearances and make sure there is an adequate fresh-air supply to
ensure sufficient cooling of the inverters. A fan for connection to the inverter is available as an
accessory (see Section15 "Accessories", page113).
500 mm
100 mm
100 mm
50 mm
300 mm