SMA Solar Technology AG 6 Electrical Connection
Installation Manual SB30-50TL-21-IA-en-21 39
6.3.3 Additional Earthing of the Enclosure
If required in the country of installation, you can use the earth terminal on the enclosure to connect a
second protective conductor or as equipotential bonding.
1. Release screw (A) and conical spring washer (B)
half-way. Use an Allen key (AF 4) to do this.
2. Insert the stripped earthing cable (D) under the
clamping bracket (C) (maximum conductor
cross-section 10 mm²).
3. Screw the clamping bracket down as follows:
Place the conical spring washer over the screw.
The grooved side of the conical spring washer must face towards the screw head.
Tighten the screw (torque: 6 Nm). Use an Allen key (AF 4) to do this.
The teeth of the conical spring washer press into the clamping bracket. The earthing cable
now has conductive connection to the enclosure.
D
A
B
C