EasyManua.ls Logo

SMA SUNNY BOY 4000TL - Connection Procedure

SMA SUNNY BOY 4000TL
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SMA Solar Technology AG Electrical Connection
Installation Guide SB30TL_40TL_50TL-IA-IEN120231 51
Connection procedure
1. Open the inverter as described in section 7.2”Opening the Inverter” (page61).
2. Loosen the cable gland's lock nut (H) slightly and
remove the filler-plug from the cable gland.
3. Insert the cable into each inverter.
4. Strip max. 8 mm off the insulated conductors.
Seal in the cable gland
There is a two-part seal in the cable gland.
Remove the internal insert if necessary, e.g. to
lay a thicker cable.
The following guideline values apply:
Cable diabmeter with seal and insert: 5 mm … 7 mm
Cable diameter with seal and without insert: 7 mm …13 mm
DANGER!
Danger to life due to high voltages in the inverter.
Do not use cables with single-layer insulation.
Strip cable to a maximum length of 15 mm.

Table of Contents

Other manuals for SMA SUNNY BOY 4000TL

Related product manuals