4 Commissioning
SMA Solar Technology AG
User Manual 33SCCPXT-E7-BA-en-58
4.5 Function Test
4.5.1 Checking the Fans
DANGER
Danger to life due to electric shock or electric arc if live components are touched
Switch off the inverter and wait at least 15minutes before opening it to allow the capacitors to discharge
completely.
Disconnect the inverter (see Section5, page50).
Procedure:
1. Switch the inverter to Stop.
2. Connect the supply voltage (see Section5.3.1, page52).
The fans start to run for a few moments.
The fans do not start up?
Contact SMAServiceLine.
4.5.2 Checking the Heating Elements and Hygrostat
Figure 11: Position of the heating element and the hygrostat
Position Designation
A Hygrostat
B Heating element
DANGER
Danger to life due to electric shock or electric arc if live components are touched
Switch off the inverter and wait at least 15minutes before opening it to allow the capacitors to discharge
completely.
Disconnect the inverter (see Section5, page50).