4 Commissioning
SMA Solar Technology AG
User Manual 41SCCPXT-E7-BA-en-58
Procedure:
1. Call up the parameter overview (see Section9.3.1, page78).
2. Set the parameter TrfVolExlHi.
3. Set the parameter VRtg.
4. Save the parameter changes (see Section9.3.2, page78).
4.6.9 Setting Project-Specific Parameters
4.6.9.1 Setting the Remote Shutdown
1. Call up the parameter overview (see Section9.3.1, page78).
2. To activate remote shutdown, set the parameter ExlStrStpEna to On (see Section10.2.1.2, page85).
3. To deactivate remote shutdown, set the parameter ExlStrStpEna to Off (see Section10.2.1.2, page85).
4. Save the parameter changes (see Section9.3.2, page78).
4.6.9.2 Deactivating the "Fully Hermetic" Transformer Protection
1. Call up the parameter overview (see Section9.3.1, page78).
2. Set the parameter ExlTrfErrEna to Off (see Section10.2.2.2 "Transformer Protection", page85)
3. Save the parameter changes (see Section9.3.2, page78).
4.6.10 Setting the String Current Monitoring
4.6.10.1 Detecting the SunnyCentralString-MonitorController and the Inverter
1. Log into the user interface (see Section9.4.1, page78).
2. Select Data > Detection.
3. In the field Total number of devices to be detected, enter the value 2.
4. Select the button [Start detection].
☑ The communication unit starts detecting all inverters and displays its progress. Once all devices have been
detected, the message ### Device detection finished ### is displayed.
☑ The devices have been detected.
4.6.10.2 Setting the Date and Time of the SunnyCentralString-MonitorController
1. Log into the user interface (see Section9.4.1, page78).
2. Select Data > Devices.
3. Select .
☑ A list of the existing device types appears.
4. Select SunnyCentralString-MonitorController.
5. Select the tab Instantaneous values.
6. Make sure that the date SysDt and time SysTm of the SunnyCentralString-MonitorController are correct.
If the settings are incorrect, change the parameters Dt and Tm .
4.6.10.3 Detecting the SunnyString-Monitors via the SunnyCentralString-
MonitorController
It may take several minutes to detect the Sunny String-Monitors, depending on the number of devices and how far
apart they are.
Procedure:
1. Log into the user interface (see Section9.4.1, page78).