7 Troubleshooting
SMA Solar Technology AG
User ManualSCCPXT-E7-BA-en-5868
Error no. Explanation Inverter behavior Corrective measures
S1 S2 R
0404* Frequency change per second too
high for grid operation
30s 30s
0502* Power frequency is too low. Power
frequency disturbance detected by
standard monitoring.
30s 30s Check power frequency.
Check the display of the grid monitoring
relay.
Make sure the fuses in the load circuit
function properly.
0503* Power frequency is too high.
Power frequency disturbance de-
tected by standard monitoring.
30s 30s
0504* Power frequency is too low. Power
frequency disturbance detected by
redundant monitoring.
30s 30s
0505* Power frequency is too high.
Power frequency disturbance de-
tected by redundant monitoring.
30s 30s
0506* The inverter has detected a stand-
alone grid and has disconnected
from the utility grid.
W W Check power frequency.
0801* One line conductor of the utility
grid has failed.
30s 30s Check the grid voltage.
Make sure the external fuses work
properly.
Make sure the AC cable connections
are tight.
0802*
1301 Left-hand rotating magnetic field is
connected.
30s Q Check the phase position.
Make sure all fuses are switched on.
1500 The conditions for grid reconnec-
tion have not yet been reached af-
ter a grid error.
W W Check the power frequency and grid
voltage.
* Depending on the parameterization, the disturbance message may have to be acknowledged manually.
7.5.4 Error Numbers 34xx to 40xx - Disturbance on the PV Array
Error no. Explanation Inverter behavior Corrective measures
S1 S2 R
3403 PV array voltage is too high. 15
min
30
min
Check the DC voltage.
Check the module wiring and system
design.
3404 Open-circuit voltage is too high.
Disturbance detected by standard
monitoring.
15
min
30
min
3406 The DC voltage is too high. 15
min
30
min