Final Inspection
Initial check:
Make sure that the internal and external check-valves (if any) of the
inlets are open and the system is pressurized in both inlets.
Make sure that the hot water that is supplied to the e-Valve reaches a
sufficient temperature (> 40
0
C).
Operation check:
Turn on the system. Press on the power dial on one of the controllers.
Wait a couple of minutes for the water temperature to sabilize.
Check the hot water, make sure that the water is comfortably hot
(38
0
C).
Use the Flow dial to toggle between outlets.
Make sure the water runs continuously through the available outlets,
over the whole toggling cycle.
Make sure that there are no leaks near the e-Valve inlet and outlet
terminals.