Hydro:Evolved Start-Up Guide
Jul 14, 2022 ©2022 Smartrise Engineering, Inc. All Rights Reserved Page 7
3 NTS Buffer Distance Up and Down
An NTS alarm may be generated in any direction during normal mode of operation. When this
occurs, the NTS buffer distance needs to be increased
The following procedure describes how to set the NTS buffer distance up and down.
Navigate to MAIN MENU | SETUP | HYDRO.
From the HYDRO SETUP menu, scroll and select NTS Buffer Distance Up or NTS Buffer
Distance Down.
From the NTS BUFFER DISTANCE UP or NTS BUFFER DISTANCE DOWN menu, enter the
buffer distance.
Scroll right and press Save.