4 Maintenance
4 - 1
4 MAINTENANCE
4-1 Daily Inspection
Check following points during usual operations. If you find some problems, immediately stop the operation and
refer to “Chapter 5 Troubleshooting” as soon as possible.
There is no air leakage
The running lamp is lighting during operation
Drain is being discharged from drain tube
The pointer of the evaporation thermometer indicates in the green zone when it is running with
pressurized air supply.
The pointer of the evaporated thermometer indicates about 3~10oC lower than that of ambient
temperature when the product is suspended with no pressurized air supply.
There is no abnormal sound or vibration coming up from the product.
There are no abnormal smell or smoke coming up from the product.
It is recommended to keep a maintenance/service record. Please refer to “Chapter 14-1 Service
Record”
4-2 Periodical Maintenance
4-2-1 Cleaning of ventilation grille (suction grille)
Clean dust and other foreign particles from the ventilation area with vacuum cleaner or air blow nozzle once a
month.
Danger
During air blowing, put on protective glass and mask to prevent dusts from coming into throat or eyes.
4-2-2 Service parts
It is recommended to replace the following parts regularly. The values shown in this operation manual
depend on the operating conditions (ambient temperature, installation environment, etc.), and they are
not guaranteed.
Table 1. List of parts to be replaced regularly
Description
Tecommended replacement interval
Pressure switch
One Million times
Fan motor
20,000 hours
Magnetic Contactor , Magnetic Switch (Note)
One Million times
*NoteOperation condition: 12 hours/day, 300 days/year,
Pressure switch open-close frequency: 1 cycle/2 minutes
(The replacement period depends on the user’s operating conditions.)
4-2-3 Cleaning of Auto Drain Strainer
Remove the dust deposited in the auto drain strainer every month. Use neutral detergent for cleaning. If they are
too dirty, replace them and shorten the period of maintenance from next time.
Auto Drain Strainer order part number
Part No.
Name
Quantity
Applicable Model
IDF-S0001
Auto Drain Strainer
1
IDFA3E , IDFA4E
IDF-S0002
Auto Drain Strainer
1
IDFA6E , IDFA8E
IDFA11E , IDFA15E

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SMC Networks IDFA3E-23-A and is the answer not in the manual?

SMC Networks IDFA3E-23-A Specifications

General IconGeneral
BrandSMC Networks
ModelIDFA3E-23-A
CategoryDehumidifier
LanguageEnglish