11 Error indication
If the error cannot be reset after the above measures are taken, then
please contact SMC.
12 Maintenance
12.1 General Maintenance
Caution
• Not following proper maintenance procedures could cause the product
to malfunction and lead to equipment damage.
• If handled improperly, compressed air can be dangerous.
• Maintenance of pneumatic systems should be performed only by
qualified personnel.
• Before performing maintenance, turn off the power supply and be sure
to cut off the supply pressure. Confirm that the air is released to
atmosphere.
• After installation and maintenance, apply operating pressure and
power to the equipment and perform appropriate functional and
leakage tests to make sure the equipment is installed correctly.
• If any electrical connections are disturbed during maintenance, ensure
they are reconnected correctly and safety checks are carried out as
required to ensure continued compliance with applicable national
regulations.
• Do not make any modification to the product.
• Do not disassemble the product, unless required by installation or
maintenance instructions.
13 Limitations of Use
13.1 Limited warranty and Disclaimer/Compliance Requirements
Refer to Handling Precautions for SMC Products.
Caution
• SMC products are not intended for use as instruments for legal
metrology.
Measurement instruments that SMC manufactures or sells have not
been qualified by type approval tests relevant to the metrology
(measurement) laws of each country.
Therefore, SMC products cannot be used for business or certification
ordained by the metrology (measurement) laws of each country.
14 Product disposal
This product shall not be disposed of as municipal waste. Check your
local regulations and guidelines to dispose of this product correctly, in
order to reduce the impact on human health and the environment.
15 Contacts
Refer to www.smcworld.com or www.smc.eu for your local distributor /
importer.
URL: https://www.smcworld.com (Global) https://www.smc.eu (Europe)
SMC Corporation, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, Japan
Specifications are subject to change without prior notice from the manufacturer.
© 2021 SMC Corporation All Rights Reserved.
Template DKP50047-F-085M
Error Type
Over
current
Error
The switch output load
current is more than
80 mA.
OFF and remove
the cause of the
over current. Then
Zero clear
Error
operation, pressure
above ±7% F.S.
(±3.5% F.S. for
compound pressure)
is applied.
After 1 second, the
mode will return to
measurement mode.
The zero clear range
can vary ±1% F.S.
with individual product
Perform zero clear
operation again
after restoring the
applied pressure to
an atmospheric
pressure condition.
Pressurize
Error
exceeded the upper
limit of the set
Adjust the applied
pressure to a level
within the set
pressure range.
lower limit of the set
System
Error
Displayed in the case
of an internal data
error.
Turn the power off
and turn it on again.
If resetting fails, an
investigation by
SMC Corporation
will be required.