52
operation (based on the number
shown in MDU’s counter OLTC
inspection and maintenance.
Regarding this, please contact
Huaming’s after-sales department.
After 300,000 times OLTC operation (based on the
number shown in MDU’s counter OLTC inspection
and maintenance. Regarding this, please contact
Huaming’s after-sales department.
operation (based on the number
Inspect the vacuum interrupters. Regarding this,
please contact Huaming’s after-sales department.
operation (based on the number
Change the diverter switch insert. Regarding this,
please contact Huaming’s after-sales department.
After 1,500,000 times OLTC
operation (based on the number
Tap selector maintenance. Regarding this, please
contact Huaming’s after-sales department.
Table13-3 Maintenance interval
Please write to export@huaming.com for any need of support.
13.3 Notice
OLTC must be maintained strictly follow the manual to ensure its good
performance. Otherwise, it will cause damages to operations of tap-changer and
transformer.
If the tap-changer does not regulate the voltage for a long time or has a tap position
that is not used for a long time, no less than 5 cycles of tap change operation should
be performed in the full tap range during a power cut.
The maintenance of the tap changer shall be performed by Huaming, and usually
the maintenance can be finished within one day