Programming
Controller ATyS
OPERATION
49
SOCOMEC - Réf.: 532 214 C
Network
nominal
frequency
Network nominal frequency 50 Hz or 60 Hz 50 Hz
PARAMETERS CHARACTERISTICS
>
Menu Setup
LCD Denomination Definition Setting Default
range values
* Refer to annexes.
(1) It might be necessary for some breakers not to set up OMR and OMF timers to 0. (2 sec.)
Type of
network*
Number of active conductors of controlled network
(refer to annexes)
1BL, 2BL,
2NBL, 3NBL,
4NBL, 41 NBL
4NBL
Network
nominal voltage
Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others
from 100 V
to 400 V
400 V
Network priority
selection
Manual
Retransfer
Activation of the feature
Keypad selection (1 or 2)
Also possible via external contact using option
1 or 2
(
or )
2
1
1 ()
1
Programming
code
modification
Possible to change the programming code from 0000 to
9999
Yes or No
1000
No
Number of
permutation
counter Reset
Allows source -> source automatic sequences
counter reset
21
Yes or No No
Type of control
logic selection
Impulse, contactor or breaker.
It might be necessary for some breakers not to set up
OMR and OMF timers to 0 (2 sec. for exemple).
Imp, con, brE Imp
Genset start
signal state
Normally opened or closed NO or NC NO
Number of
auxiliary contact
Depending on the number if available auxiliary contacts
(switch, contactor, breaker)
0, 2, 3 2
12
Parameter 1,
return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes or No No
12
Parameter 2
return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes or No No
12