What to do if the Socomec Industrial Electrical product does not switch over after the priority source is lost?
- Jjohn68Nov 22, 2025
If the product doesn't switch over after the priority source is lost, check the following: * Back-up source availability. * Back-up source voltage and frequency thresholds and hystereses and modify if required. * That the product selector switch is in AUTO. * That automatic operation has not been inhibited by external orders. * Priority source voltage and frequency thresholds and hystereses and modify if necessary. * That the time-delay 1RT (Source 1 Return Timer) has counted down, and that it is not too long. (The display indicates 1RT xxxSEC). * That the "manual retransfer" function is not activated. If this function is unnecessary: In the SETUP menu, the RETRANS variable must be at NO. * That automatic operation has not been inhibited by external orders. * That the IN...