www.socomec.com
ATySp
Automatic Transfer Switching Equipment
EN
INSTRUCTION
MANUAL

Table of Contents

Other manuals for socomec ATyS g

Questions and Answers

  • J
    Jennifer AyersNov 22, 2025
    What to do if the Socomec Industrial Electrical product does not switch over after the priority source is lost?
    • J
      john68Nov 22, 2025
      If the product doesn't switch over after the priority source is lost, check the following: * Back-up source availability. * Back-up source voltage and frequency thresholds and hystereses and modify if required. * That the product selector switch is in AUTO. * That automatic operation has not been inhibited by external orders. * Priority source voltage and frequency thresholds and hystereses and modify if necessary. * That the time-delay 1RT (Source 1 Return Timer) has counted down, and that it is not too long. (The display indicates 1RT xxxSEC). * That the "manual retransfer" function is not activated. If this function is unnecessary: In the SETUP menu, the RETRANS variable must be at NO. * That automatic operation has not been inhibited by external orders. * That the IN...
  • T
    Tonya HermanAug 25, 2025
    What to check if nothing happens following a loss of the priority source on Socomec Industrial Electrical (application Main-Gen)?
    • N
      Nancy DavidsonAug 26, 2025
      If nothing happens following a loss of the priority source (application Main-Gen), you should: * Check the setting of 1FT. After 1FT has counted down 71-72-74 should change state. * Check the status of the "gen set start" contact (contact 71-73-74) after 1FT countdown. * Check the wiring from the "gen set start" contact (71-72-74) to the generating set controller.
  • L
    Linda BraunAug 26, 2025
    Why is the fault LED on the Socomec Switch (Motorisation) illuminated?
    • C
      Courtney MillerAug 26, 2025
      The FAULT / MANUAL LED on the motorisation module is on when in manual mode (this is normal) and in AUT Mode when there is an internal fault in the ATyS t. To reset a fault condition, switch the ATyS t from AUT to Manu and back to AUT. If the fault LED remains on, you will need to localize and clear the fault prior to reset. The FAULT / Manual LED will also be on when contact 313 is closed with 317, force the ATyS to off position. The FAULT LED will also illuminate when the aux power supply is present but out of range.
  • J
    James ClarkAug 27, 2025
    How to fix a flashing ready light on a socomec ATyS g Switch?
    • B
      Brian RobertsAug 27, 2025
      The Ready light flashes to indicate that the saved configuration is not identical to what is displayed on the ATS controller. To get a steady READY light either revert to the settings in the ATyS t or save the new settings. To save, put into manual mode and press the PROG OK button momentarily.
  • S
    Sean SextonNov 27, 2025
    What to do if ATyS t socomec ATyS g Switch does not operate electrically?
    • B
      brownadamNov 27, 2025
      To resolve this, verify the power supply on terminals 101-102 and 201-202: 208 - 277 Vac ±20 %. Also, verify that the front selector switch is in the (AUT) position. Check that contacts 313 and 317 are open. Verify that the power LED (Green) is On whilst the fault LED (RED) is off. Ensure that the Ready light on the ATS controller is a steady Green light. Verify presence of at least one green LED on the source supply available LED’s. Verify that the product is available with contacts 63A / 64A and 63B / 64B closed. Verify whether the problem is limited to the ATS controls + the motorisation module or just the ATS controls. To isolate the fault to the ATS controller or the complete unit, close contacts 312 with 317 whilst ensuring that 313 and 317 remain open. This will force the ATyS t int...
  • C
    Carmen WilkinsonSep 15, 2025
    What to do if electrical operation does not correspond to external order I,O,II on Socomec Industrial Electrical?
    • K
      kevinwilsonSep 16, 2025
      If the electrical operation does not correspond to external order I,O,II, you should: * Verify the selected control logic wiring (impulse or contactor). * Verify the connector connections.
  • J
    Joshua HarrisSep 13, 2025
    Why does the fault LED turn on in Socomec Industrial Electrical (ATS Controller)?
    • M
      Michael WagnerSep 14, 2025
      The fault LED on the ATS Controller might be on because an external fault/alarm condition is active through one of the ATyS configurable inputs. This is normal and can be reset by opening the associated contact input. To attempt to solve the problem, switch the ATyS p from AUT to Manual and back to AUT.
  • D
    dennisadrienneSep 14, 2025
    Why is the SOURCE availability indicator not illuminating on my Socomec Industrial Electrical device?
    • K
      Kenneth SmithSep 15, 2025
      If the SOURCE availability indicator does not illuminate when the source is available, try the following: * Press the "LED test" button and ensure that the corresponding LED’s illuminate. * Check in programming mode that the nominal voltage value (by default set to 400V), the nominal frequency value and the network configuration correspond to the network and modify if necessary. * Check the voltage and frequency thresholds and hysteresis for this source, in the Volt and Frequency menus and modify if necessary.
  • J
    Joshua ChristianSep 6, 2025
    Why is it not possible to manually operate the socomec Switch?
    • A
      Anthony HarrisSep 6, 2025
      If you cannot manually operate the Socomec switch, please check the following: * Ensure that the front selector switch is in the Manual position. * Confirm that the product is not padlocked. * Verify the rotation direction of the handle. * Apply a sufficient progressive action in the direction indicated on the handle.
  • M
    Matthew PrinceSep 3, 2025
    Why is it impossible to padlock my Socomec Switch?
    • D
      Dominique CarpenterSep 3, 2025
      To resolve this, verify that the front selector switch is in the manual position, ensure that the emergency handle for manual operation is not inserted into the ATyS manual slot, and verify that the ATyS is in the 0 position. Padlocking is only possible in the 0 position for standard products.

socomec ATyS g Specifications

General IconGeneral
Rated frequency50 / 60 Hz
Pollution degree3
OperationAutomatic or manual
Operating temperature range-25 to +70 °C
Storage temperature range-40°C to +85°C
Relative humidity95%
Altitude2000 m
MountingDIN rail
StandardsIEC 60947-6-1
Poles3 or 4