ATySpM
Automatic Transfer Switching Equipment
EN
INSTRUCTION
MANUAL
www.socomec.com

Table of Contents

Questions and Answers

  • D
    Debra HudsonAug 15, 2025
    What to do if socomec ATyS p M does not switch over after priority source is lost?
    • B
      Brandon HollandAug 16, 2025
      If the Socomec Switch does not switch over after the priority source is lost, first verify that the device is not in manual mode by ensuring the cover is closed for automatic mode. Also, check that automatic operation is not being blocked by external commands. Finally, examine the Emergency Source Availability LED; if it's off, consult the relevant troubleshooting steps for that specific issue.
  • D
    Danielle SmithAug 19, 2025
    What to do if socomec ATyS p M does not switch over when the priority source is restored?
    • S
      scottmalloryAug 19, 2025
      If the Socomec Switch does not switch over when the priority source is restored, ensure that the product is not in manual mode by checking that the cover is closed for automatic mode. Also, verify that automatic operation is not inhibited by external orders. Check the state of the "Priority Source Availability" LED and refer to the relevant troubleshooting if it is off. Verify the setting of the 1RT (1 Return Timer) and use a stopwatch to check the switch to Priority SOURCE (duration of this delay is between 0 and 3600s). Finally, check that the manual retransfer function is not active in the SETUP menu by setting RETRANS to NO.
  • S
    Sara HowardAug 22, 2025
    What to do if Socomec Switch cannot be switched over using the handle?
    • D
      David SkinnerAug 22, 2025
      If the Socomec Switch cannot be switched over using the handle, check the direction of rotation of the handle: manual switchover from position 1 to position 2 is executed clockwise, and the return operation is executed anticlockwise. Ensure that the product is not padlocked. Use the handle extension on the ALLEN key to check that the appropriate adjustment torque is applied. When using a single AC, ensure that the length of the screws used is not greater than 20 mm.
  • D
    Daniel GonzalezAug 25, 2025
    How to fix the "Priority SOURCE Availability" LED when it does not come on a Socomec Switch?
    • K
      Kevin MonroeAug 25, 2025
      If the "Priority SOURCE Availability" LED does not come on for the Socomec Switch, begin by pressing the "LED test" button. Next, check the display for the message "F13 ROT-1" (Priority Source Phase Rotation Fault) and verify phase rotation consistency between the source and the ROT parameter in the SETUP menu, or between the 2 sources. Also, check the network type, nominal voltage, and frequency parameters in the SETUP menu, and voltage and frequency thresholds in the VOLT LEVELS and FREQ LEVELS menus. If using an Auto transformer, configure the NETWORK parameter to 3NBL and the NEUTRAL parameter (location of Neutral) to left or right in the SETUP menu.
  • P
    Patricia WilliamsAug 27, 2025
    What to do if the "Emergency SOURCE Availability" LED does not come on for socomec ATyS p M Switch?
    • A
      Alexander FarleyAug 27, 2025
      If the "Emergency SOURCE Availability" LED does not come on for the Socomec Switch, press the "LED test" button. Check the display for the message "F23 ROT- 2" (Emergency Source Phase Rotation Fault) and verify phase rotation consistency between the source and the ROT parameter in the SETUP menu, or between the 2 sources. If a generator is operating off load, check the nominal voltage threshold and hysteresis in the VOLT LEVELS menu and the frequency threshold and hysteresis in the FREQ LEVELS menu. Also, check the network type, nominal voltage, and frequency parameters in the SETUP menu. If using an Auto transformer, configure the NETWORK parameter to 3NBL and the NEUTRAL parameter (location of Neutral) to left or right in the SETUP menu.
  • C
    carolyn56Aug 31, 2025
    What to do if socomec ATyS p M Switch remains switched off after the priority source is lost?
    • S
      Steven MendozaAug 31, 2025
      If the Socomec Switch remains switched off after the priority source is lost, check for a voltage of 106 to 305 Vac on terminals 1-7 corresponding to source II (for Model 230/400 Vac). For a Transformer/Generator application, confirm that the 1FT (1 Failure Timer) has counted down using a stopwatch. If GE START = NO (Normally Open) in the SETUP menu: Contact 73-74 Closed means Generator starting order and Contact 73-74 Open means Generator stoppage order. If GE START = NC (Normally Closed) in the SETUP menu: Contact 73-74 Closed means Generator stoppage order and Contact 73-74 Open means Generator starting order.
  • T
    Theresa MclaughlinSep 3, 2025
    Why does the Emergency Source continue to operate after returning to Priority SOURCE on socomec ATyS p M?
    • V
      Vicki MooreSep 3, 2025
      If the Socomec Switch returns to the priority source but the emergency source (for a generator) continues to operate, check that the 2CT (2 Cool Timer) counts down (duration between 0 and 600s) using a stopwatch. Contact 73 - 74 should change state once this delay has counted down. If GE START = NO (Normally Open) in the SETUP menu: Contact 73-74 Closed means Generator starting order and Contact 73-74 Open means Generator stoppage order. If GE START = NC (Normally Closed) in the SETUP menu: Contact 73-74 Closed means Generator stoppage order and Contact 73-74 Open means Generator starting order. Also, verify the product is in Automatic mode (cover closed), and that automatic operation is not inhibited by external orders.
  • R
    Rebecca CaldwellSep 5, 2025
    How to start ON LOAD and OFF LOAD tests via the keypad on Socomec Switch?
    • C
      Cheyenne HodgesSep 5, 2025
      If ON LOAD and OFF LOAD tests cannot be started via the keypad on the Socomec Switch, verify that the product is in Automatic mode (cover closed) and that automatic operation has not been inhibited by external orders. Check the Operating mode password (factory code 0000) to access the test functions. Ensure that the product is in M-G application. Finally, check the state of the "Priority Source Availability" LED and refer to the symptom concerned if it is off.
  • K
    Kaitlyn BowmanSep 8, 2025
    Why is AUTOMATIC mode not activated even though the cover is closed on socomec ATyS p M?
    • L
      Linda DiazSep 9, 2025
      If AUTOMATIC mode is not activated on the Socomec Switch even though the cover is closed, verify that the plastic pin (sensor) is in place on the bottom of the cover, as this pin activates the sensor which indicates the position of the cover (open or closed). Also, check that automatic operation has not been inhibited by external orders.
  • M
    Mike MejiaSep 12, 2025
    Why the socomec ATyS p M Switch cannot be locked?
    • S
      Sandy WileySep 12, 2025
      To resolve the issue of a Socomec Switch that cannot be locked, check the mechanical position of the changeover switch. Locking is only possible in position 0 as standard. Locking in positions 1-0-2 is possible by modifying the product in accordance with the instructions.

Summary

General Safety Instructions

Introduction to ATYS p M

ATYS Family Product Range

Overview of the ATyS product family and their applications.

ATYS M Range Key Features

ATYS M Selection Guide

Comparison table of ATYS M models based on applications and functions.

Quick Start Installation and Commissioning

Installation Procedures

Installation, Padlocking, and Power Connections

Details on installation orientation, padlocking, and power terminal connections.

ATYS P M Versions

Product Presentation and Specifications

Overview of ATYS p M versions, features, and technical specifications.

Optional Accessories

Technical Data

Environmental Conditions

Product Installation

Mounting Configurations

Details on changing padlocking, orientation, dimensions, and back plate mounting.

DIN Rail Mounting

Power Circuit Connections

Ratings and Cable Cross-sections

Table correlating current ratings with required cable cross-sections.

Single-Phase Parallel Pole Setup

Guidelines for using a 4P device in single-phase with parallel poles.

Network Configurations

Voltage Configurations for 230;400 VAC

Wiring diagrams for 230/400VAC versions based on network types.

Voltage Configurations for 127;230 VAC

Three Phase Without Neutral Network

Control and Command Circuit Connections

Terminal Designations and Auxiliary Contacts

Identification of terminals, connectors, and auxiliary contact schedules.

Product Operation Overview

Interface, Manual Mode, and Padlocking

Overview of the product interface, manual operation, and padlocking procedures.

Front Keypad Navigation and Information

Keypad, Display, and Event Management

Guide to keypad functions, display, event encoding, and error message lists.

Programming the ATYS p M

Programming Methods and Modes

Information on programming via EasyConfig, keypad, and different modes.

Configuration Setup Menu

Phase Rotation Check

Voltage and Frequency Settings

Timer Settings

I-O Menu and Input;Output Descriptions

Communication Settings

Automatic Mode Operations

Automatic Mode and Sequences

Procedures for automatic mode and flowcharts for source loss/restoration.

Control and Test Operating Modes

Test Modes and Procedures

Detailed procedures for performing off-load, on-load tests, and position checks.

Emergency Breaking (Trip Function)

Communication Features

COMM Menu and Modbus Protocol

Settings for communication, Modbus protocol, and register mapping.

Preventative Maintenance

Troubleshooting Guide

socomec ATyS p M Specifications

General IconGeneral
Product CategoryTransfer switch
Frequency50/60 Hz
Protection DegreeIP20
Number of Poles4
Poles4
Voltage400V AC
ControlAutomatic
Storage Temperature-40°C to +85°C
StandardsIEC 60947-6-1
MountingDIN rail
Rated Current63A to 125A
Rated Operational Current63A to 125A
Rated Current (Ith)63A to 125A