57
EN
ATySpM - 542935E - SOCOMEC
13.6.5. Priority source loss sequence (with trip) in M-M application
Conguration
- APP = M-M : Mains - Mains application
- RETURN 0 = YES: : the changeover switch switches to position 0 (open) during loss of the source
Transfer I--> 0
2nd trip function
2nd trip function *
Transfer 0--> II
*
Transfer 0--> I
• Priority source unavailable
• Emergency source available
• Switch in position II
• Priority source available
• Emergency source available / unavailable
• Switch in position I
Priority source
present?
Position 0 or II? End 1RT dyn? 2nd TRIP?
End 1FT?
Emergency source
present?
Variable 2nd trip
= Yes ?
Is the capacitor
loaded?
End 0DT
End 1OT?
No
No
No
No
No
Yes
Yes
and
Yes
Yes Ye s Ye s Yes
Yes
No
No
No
No No