13.6.7. Priority source automatic restoration sequence
This sequence is started as soon as the system is in AUTO mode and in position II.
• Specic function
Automatic retransfer inhibited:
- Once source
I
is restored, it may be preferable not to retransfer the load from source
II
to source
I
immediately.
- Once the retransfer from source
II
to source
I
is possible, the RETRANS function locks the retransfer, and the
AUT LED ashes pending the operator’s conrmation.
- The VALIDATION button must be pressed or an input programmed on RTC to authorise the retransfer.