13.9.4. Function 3
Dec. address. Hex. address. No. of words Designation Unit
Status
20480 5000 1
Type of network
1 : 127 - 230 V
2 : 230 - 400 V
20481 5001 1
Operating mode
0x0000: Manual mode
0x0010: Automatic mode
0x0020: Control mode
0x0040: Inhibited mode
20482 5002 1
Position
1: Position 0
2 : Position I
3 : Position II
20484 5004 1
Genset starting order status, source
II
0: Inactive
1: Active
20485 5005 1
Priority
0: Network
1 : Source
I
2 : Source
II
20486 5006 1
Source
I
status
0: No source
1 : Out of thresholds
2: Available
20487 5007 1
Source
II
status
0: No source
1 : Out of thresholds
2: Available
20488 5008 1
Test in progress
0x0000: None
0x0001: TOF
0x0002: EOF
0x0004: TON
0x0008: EON
20489 5009 1
Cycle counter
20490 500A 1
Operations to position I counter
20491 500B 1
Operations to position II counter
20492 500C 1
Fault signal
0: None
1 : Alarm
2 : Fault
20493 500D 1
Alarm / fault code
0: None
1 : F00 Op Fct
2 : F03 Neutral
3 : F11 FLT - 1
4 : F21 FLT - 2
5 : F12 ALR - 1
6 : F22 ALR - 2
7 : F13 ROT - 1
8: F23 ROT - 2
9: F14 CAP - 1
10 : F24 CAP - 2
11 : F15 PWR - 1
12 : F25 PWR - 2
13 : F16 POS - 1
14 : F26 POS - 2
15: F06 POS - 0
20494 500E 1
Cause of last switchover
0 : None
1 : Manual
2 :
under-voltage
I
3 : under-voltage
II
4 :
Overvoltage source
I
5 : Overvoltage source
II
6 :
Source under-frequency
I
7 : Source under-frequency
II
8 :
Source over-frequency
I
9 : Source over-frequency
II
10 : Source
phases unbalanced
I
11 : Source
II
12: Direction of rotation inverted on source
I
13 : Direction of rotation inverted on source
II