117
EN
ATYSp - 542001E - SOCOMEC
Dec.
Address
Hex.
Address
Words
count
Description Unit
23041 5A01 1 In 6 - StartGen board input 2 function
0: --- - None
1: INH - Inhibition
2: TON - Test on load
3: TOF - Test off load
4: EON - External order on load
5: EOF - External order off load
6: RTC - Retransfer
7: PRI - Priority
8: SS1 - Validation Stabilization source 1
9: SS2 - Validation Stabilization source 2
10: AL1 - Alarm 1
11: AL2 - Alarm 2
12: FT1 - Fault 1
13: FT2 - Fault 2
14: MSR - Power priority
15: OA1 - Override source 1 available
16: OA2 - Override source 2 available
17: RST - Reset faults state
18: LSI - Load shedding
19: TR1 - Time Range1 Validate
20: TR2 - Time Range2 Validate
21: TR3 - Time Range3 Validate
22: TR4 - Time Range4 Validate
24: CHP - Change of position
23042 5A02 1 In 5 - Input n°5 state
0: NO
1: NC
23043 5A03 1 In 6 - Input n°6 state
0: NO
1: NC
23044 5A04 1 In 1 - Ext display connector board input 1 function
0: --- - None
1: INH - Inhibition
2: TON - Test on load
3: TOF - Test off load
4: EON - External order on load
5: EOF - External order off load
6: RTC - Retransfer
7: PRI - Priority
8: SS1 - Validation Stabilization source 1
9: SS2 - Validation Stabilization source 2
10: AL1 - Alarm 1
11: AL2 - Alarm 2
12: FT1 - Fault 1
13: FT2 - Fault 2
14: MSR - Power priority
15: OA1 - Override source 1 available
16: OA2 - Override source 2 available
17: RST - Reset faults state
18: LSI - Load shedding
19: TR1 - Time Range1 Validate
20: TR2 - Time Range2 Validate
21: TR3 - Time Range3 Validate
22: TR4 - Time Range4 Validate
24: CHP - Change of position