ATYSp - 542001E - SOCOMEC
1
SETUP
Definition AdjustmentRange M-G M-M
CT SEC 5
Current Transformer secondary rating 1A
2A
S1=SW2 NO
Inverted power section switch wiring. Switch
1 (Front) cabled as Switch 2 and Switch 2
(Back) cabled as Switch 1.
NO: Not Inverted
YES: Inverted
NO
YES
BACKLGHT INT
The LCD backlight may be set to:
OFF: Always Off
ON: Always On
INT: On after pressing the keypad and during
operating sequences only. (Turned off after 2
minutes of inactivity).
OFF
ON
INT
CODE P 1000
Password Code to modify and save settings
in Programming Mode.
Default factory setting: 1000
0000 to 9999
CODE E 0000
Password Code to modify and save settings
in Operating Mode.
Default factory setting: 0000
0000 to 9999
BACKUP SAVE
Save the settings in the backup so as to recall
them later within the same menu.
Load to charge the backup data
SAVE
LOAD
AnnexeI-6.1.**Phaserotationcheck:
This functionality checks the consistency of phase rotation i.e. of the wiring prior to commissioning.
Example: If the parameter ROT PH = ABC:
L1 (A)
L2 (B)L3 (C)
OK
L1 (A)
L3 (C)L2 (B)
NON OK
Display
12
or
12
depending on the non-compliant source
(Rotation check on sources
1
and
2
).
WARNING
Function available on both sources in case of 4NBL/4BL or 3NBL/3BL type of
network and only on source
1
in case of 41NBL or 42NBL network.