EasyManua.ls Logo

socomec ATyS p - Annexe II - 4. Configuration navigation screen

socomec ATyS p
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
112
EN


1
SETUP
2
VOLT. LEVELS
3
FREQ. LEVELS
4
PWR. LEVELS
5
TIMERS VALUE
6
I-O
7
COMM

8
DATE/TIME
NETWORK 4NBL OV. U I 115% OV. F I 105% OV.P I 0000 kVA 1FT 0003 SEC IN 1 --- NO DHCP NO  YEAR
AUTOCONF NO  OV. U HYS I 110% OV. F HYS I 103% OV.P HYS I 0000 kVA 1RT 0180 SEC IN 2 --- NO IP 1-2 192.168.

MONTH
NEUTRAL AUTO UND. U I 085% UND. F I 095% OV.P I I 0000 kVA 2FT 0003 SEC IN 3 --- NO IP 3-4 .002.001 DAY
ROT PH. --- UND. U HYS I 095% UND. F HYS I 097% OV.P HYS I I 0000 kVA 2RT 0005 SEC  IN 4 --- NO GAT1-2 000.000.

HOUR
NOM. VOLT 400 V UNB. U I 00% OV. F I I 105% 2AT 0005 SEC  IN 5 --- NO GAT3-4 .000.000 MINUTE
NOM. FREQ 50 Hz UNB. U HYS I 00% OV. F HYS I I 103% 2CT 0180 SEC  IN 6 --- NO MSK1-2 255.255.

SECOND
APP M-G OV. U I I 115% UND. F I I 095% 2ST 0030 SEC  IN 7 --- NO  MSK3-4 .255.000
PRIO TON NO  OV. U HYS I I 110% UND. F HYS I I 097% ODT 0003 SEC IN 8 --- NO  ADDRESS 005
PRIO EON NO  UND. U I I 085% TOT UNL  IN 9 --- NO  BDRATE 9600
PRIO NET 1  UND. U HYS I I 095% TOT 0010 SEC  IN10 --- NO  STOP BIT 1
RETRANS NO UNB. U I I 00% T3T 0000 SEC  IN11 --- NO  PARITY NONE
CT PRI 100 UNB. U HYS I I 00% TFT UNL 
IN12 --- NO 
CT SEC 5 TFT 0600 SEC  IN13 --- NO 
S1=SW2 NO E1T 0005 SEC  IN14 --- NO 
BACKLGHT INT E2T UNL  OUT 1 POP NO
CODE P 1000 E2T 0010 SEC  OUT 2 --- NO 
CODE E 0000 E3T 0005 SEC  OUT 3 --- NO 
BACKUP SAVE E5T 0005 SEC  OUT 4 --- NO 
E6T LIM  OUT 5 --- NO 
E6T 0600 SEC  OUT 6 --- NO 
E7T 0005 SEC  OUT 7 --- NO 
LST 0004 SEC  OUT 8 --- NO 
EET 0168 H  OUT 9 --- NO 
EDT 1800 SEC 
(1) When "APP" is set to "M-G"
(2) When "APP" is set to "M-M"
(3) When one of the I/P is set to "EON"
(4) When one of the I/P is set to "EOF"
(5) When one of the O/P is set to "LSC"
(6) When one of the O/P is set to "EES"
(7) If the product is in manual mode
(8) With optional I/O modules
(9) With Ethernet module
(10) Only if a communication module is used


Press 5s
Go To
1
SETUP
Scroll to
AUTOCONF
Enter code 1000
Set to
YES
Press 60 ms

Save : press 5s