7. ENVIRONMENTAL CONDITIONS
Humidity
80 % humidity without condensation at 55°C
95 % humidity without condensation at 40°C
Temperature
-20 +40°C without de-rating
40 °C < t ≤ 70 °C with de-rating (see Technical Characteristics)
Altitude
Up to 2000m
Correction factors:
2 000 m < A ≤ 3 000m 3 000 m < A ≤ 4 000m
UE 0.95 0.80
Ie 0.85 0.85
Storage
1 year maximum
Maximum storage temperature: +55 °C
80 % humidity without condensation at 55°C
ø 1 mm
IP rating
IP41 in the SOCOMEC polycarbonate modular enclosure see page page 18
IP2x for non-enclosed modular product
Protection class: Class 1