EasyManua.ls Logo

socomec COUNTIS ATv2 - Configuration

socomec COUNTIS ATv2
10 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SOCOMEC - Ref. : 875 645 D
7
E NG LI S H
CONFIGURATION
KEY INSTRUCTION
For 3 seconds to access
access-code entry (CdE).
Note
:
The device will automatically leave
the configuration menu if no buttons
are pressed for a period of 25
seconds.
Note:
Press the t button for a prolonged
period to scroll rapidly through the
configuration scr
eens. Press for a
short period to scroll through each
screen one-by-one.
Note
:
A long press on the button t causes
rapid scrolling and a single short
press causes scrolling in steps of 5.
Note:
The values available depend on the
Ct ratio.
To enter code 21.
T
o validate the code and access to
the network programming (nET).
To select the network type, 1bL
(single phase), 2bL (two-phase),
3-4 nbL (unbalanced three-phase)
and 3-4 bL (balanced three-phase).
To validate the network programming
and go on to the current transformer
(CT) primary value.
T
o programme the primary value up
to 6000 A.
To validate the unit programming and
go on to the pulse output (PuLSES).
To go on to the weight of this output
(VAL).
To select the weight “0.1” for
0.1
kWh, “1” for 1 kWh, “10” for
10
kWh, “100” for 100
kWh.
To validate the programming of this
weight and go on to the pulse
duration (dur).
To select the duration from 60 to
900 ms.
To accept value and pass to partial
meter zero reset (rSET).
T
o select ‘rSEt nO’ (no reset to zero)
and ‘rSEt YES’ (reset to zero).
To confirm reset to zero and return to
network type pr
ogramming.
+
To confirm and quit programming.
+

Related product manuals