22 EN
COUNTIS E03/E04 - 545865A - SOCOMEC
13. CHARACTERISTICS
GENERAL FEATURES
Compliant with
European EMC Directive No. 2014/30/EU dated 26/02/2014 LV Directive No.
2014/35/EU dated 26/02/2014
Measuring Instrument Directive MID No. 2014/32/EU dated 26/02/2014
EN50470-1/-3
IEC 62053-21/-23
Frequency 45 and 65 Hz
Power supply Self-supplied
Rated dissipated power (Wmax.) 1.5 VA - 1 W
FEATURES
Single-phase connectivity 2 wires 230 V
Stores energy readings and settings In the EEPROM memory
Identifies display of tariffs T1 and T2
CURRENT MEASUREMENTS
Type Single-phase - direct 40 A
Input consumption 0.5 VA
Start-up current (Ist) 20 A
Minimum current (Imin) 0.25 A
Transition current (Itr) 0.5 A
Reference current (Iref) 5 A
Permanent overload (lmax) 40 A
Intermittent overload 30 Imax for 1/2 cycle
OVERLOAD CAPACITY
DC voltage Un 276 VAC
Realtime voltage Un (1 s) 300 VAC
DC current Imax 40 A
Realtime current Imax 30 Imax for 1/2 cycle
VOLTAGE MEASUREMENTS
Range of measurement 230 ± 20%
Power consumption 7.5 VA max
Permanent overload 280 V phase-neutral
FREQUENCY MEASUREMENT
Frequency measurement 45-65 Hz
ENERGY MEASUREMENT
Active Yes
Reactive Yes
Total and partial reading Yes
MID metering Bidirectional with single-phase
Resolution 10Wh, 10 varh
ENERGY ACCURACY
Active energy Ea+
Class B (EN 50470-3) E04
Class 1 (EN 62053-21)
Reactive energy Er+ Class 2 (EN 62053-23)