123
DELPHYS MX ELITE
250-900 kVA
SPECIFICATIONS
Electrical characteristics - Bypass
Model MX 250 MX 300 MX 400 MX 500 MX 800 MX 900
Bypass frequency variation speed 2 Hz/s settable
Bypass rated voltage Rated output voltage ±10%
Bypass rated frequency 50/60 Hz selectable
Bypass frequency tolerance ±2 Hz (from 0.2 to 4 Hz settable (operation with generator unit))
Electrical characteristics - Inverter
Model MX 250 MX 300 MX 400 MX 500 MX 800 MX 900
Rated output voltage (selectable) 380/400/415 V
Output voltage tolerance
Static: < 1%
Dynamic: (0-100% Pn) ±2%
Rated output frequency 50/60 Hz (selectable)
Output frequency tolerance 0.02 on mains power failure
Load crest factor 3:1
Voltage harmonic distortion
< 2% on linear load
< 4% on distorting load (Ph/N)
< 2% on linear load
< 3% on distorting load (Ph/N)
Overload tolerated by the inverter
(with mains power present)
125% x 10 min
150% x 1 min
Electrical characteristics - Efficiency
Model MX 250 MX 300 MX 400 MX 500 MX 800 MX 900
Double conversion efficiency
(normal mode)
93.5% at full load 93.5% at full load
Efficiency in Eco Mode 98%
Electrical characteristics - Environment
Model MX 250 MX 300 MX 400 MX 500 MX 800 MX 900
Storage temperatures
-20 +70 °C (-4-158 °F) (15-25 °C for best battery life)
Working temperature
10 °C to +35 °C (50-95 °F)
(15-25 °C
for best battery life
)
10 °C to +35 °C (50-95 °F)
(1)
Maximum relative humidity
(non-condensing)
95%
Maximum altitude without derating 1000 m (3300 ft)
Degree of protection IP20 (up to IP52 optional)
Portability EN 60068-2
Colour RAL 9006 (Grey Toyo)
(1) Condition apply.