125
DELPHYS MX ELITE
250-900 kVA
6.1. Overview
The construction of the equipment and choice of materials and components comply with all current laws, decrees, directives and
standards currently in force.
In particular, the equipment is fully compliant with all European Directives concerning CE marking.
2006/95/EC Council Directive 2006/95/EC, dated 16 February 2007, on the reconciliation of legislation within Member States
regarding electrical material for use within specific voltage ranges.
2004/108/EC Council Directive 2004/108/EEC, dated 15 December 2004, on the harmonisation of legislation within Member
States regarding electromagnetic compatibility, in abrogation of directive 89/336/EEC.
6.2. Standards
6.2.1. Electromagnetic compatibility
Electromagnetic Compatibility Provisions (EMC)
EN 62040-2. Electromagnetic compatibility (class C3 standard - C2 optional)
EN 61000-2-2 Compatibility levels for low-frequency conducted disturbances and signalling in public low-voltage power supply
systems
EN 61000-4-2 Electrostatic discharge immunity test,
EN 61000-4-3 Radiated radio-frequency electromagnetic field immunity test,
EN 61000-4-4 Electrical fast transient/burst immunity test,
EN 61000-4-5 Surge immunity test,
EN 61000-4-6 Immunity to conducted disturbances, induced by radio-frequency fields.
EN 55011 class A Limits and methods of measurement of radio disturbance characteristics of industrial, scientific and medical (ISM)
radio-frequency equipment.
6.2.2. Safety
General and safety requirements for UPS used in operator access areas
EN 60950-1 General and safety requirements for equipment used in operator access areas
EN 62040-1 General and safety requirements for UPS used in restricted access locations
EN 60439-1 Low-voltage switchgear and controlgear assemblies - Part 1: Type-tested and partially type-tested assemblies,
EN 50272-2 Safety requirements for secondary batteries and battery installations
EN 60896-1 Stationary lead-acid batteries. General requirements and methods of test. Part 1: Vented types
EN 60896-2 Stationary lead-acid batteries. General requirements and methods of test. Part 1: Valve-regulated types
EN 60146 Semiconductor convertors
EN 60529 Degrees of protection provided by enclosures
6.2.3. Type and performances
Performance requirements and methods of test
EN 62040-3 Uninterruptible power systems (UPS). Methods of specifying the performance and test requirements
6.3. System and installation guidelines
Once installed in a system, the UPS will not alter the neutral conditions; this is because the neutral input terminal “N” is connected
directly to output terminal “N1” inside the equipment. If the neutral condition of the system downstream of the UPS needs modifica-
tion, it will be necessary to install the IP version or to use the isolation transformer option.
The regulations refer to the unit (UPS) to which the manufacturer must comply with. The UPS engineer adhere’s to current legislation
for the specific electrical system (e.g. EN 60364).
6. REFERENCE STANDARDS AND DIRECTIVES

Other manuals for socomec DELPHYS MX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the socomec DELPHYS MX and is the answer not in the manual?

socomec DELPHYS MX Specifications

General IconGeneral
Brandsocomec
ModelDELPHYS MX
CategoryUPS
LanguageEnglish

Related product manuals