55
DIRIS A40/A41 - Ref.: 535 747 A
DIRIS A40 / A41
TECHNICAL CHARACTERISTICS
CE MARKING
The DIRIS A40/A41 complies with :
The requirements of the European directive on electromagnetic compatibility (EMC) no. 89/336/CEE dated 3 May 1989,
modified by directive no. 92/31/CEE dated 28 April 1992 and by directive no. 93/68/CEE dated 22 July 1993.
Low voltage directive no. 73/23/CEE dated 19 February 1973, modified by directive no. 93/68/CEE dated 22 July 1993
modified by directive no. 2006/95/CE.
ELECTROMAGNETIC COMPATIBILITY
Immunity to electrostatic discharges: IEC 61000-4-2 - Level III
Immunity to radiated radio-frequency fields: IEC 61000-4-3 - Level III
Immunity to electrical fast transients/bursts: IEC 61000-4-4 - Level IV
Immunity to impulse waves: IEC 61000-4-5 - Level IV
Immunity to conducted disturbances: IEC 61000-4-6 - Level III
Immunity to power frequency magnetic fields: IEC 61000-4-8 - Level IV
Conducted and radiated emissions: IEC 61000-6-4 - Class B
Immunity to voltage dips and short interruptions: IEC 61000-4-11
CLIMATE
Operating-temperature range: IEC 60068-2-1/IEC 60068-2-2
-10 °C to +55 °C
Storage temperature range: IEC 60068-2-1/IEC 60068-2-2
-20 °C to +85 °C
Humidity: IEC 60068-2-30 - 95 %
Saling fog: IEC 60068-2-52 - 2,5 % NaCl
MECHANICAL CHARACTERISTICS
Vibration from 10 to 50 Hz : IEC 60068-2-6 - 2 g
INSULATION
Installation category: III (480VAC ph/ph)
Degree of pollution: 2
Rated impulse withstand voltage: IEC 60947-1 - V imp: 4 kV
Front face: Classe II
Electric security: IEC 61010-1
GB
CARACTÉRISTIQUES DES «FONCTIONS D’ÉVALUATION DE LA QUALITÉ DE L’ALIMENTATION»
Symbols for functions Measurement range Operating performance class,
according to CEI 61557-12
Other additional
specifications
KI 1000 100 10 1
f 45 to 65 Hz 0,02 - - - -
I 0,1 to 1,2 A for TC 1A
0,5 to 6 A for TC 5A
0,2
--- -
In, Inc 0,1 to 1,2 A for TC 1A
0,5 to 6 A for TC 5A
0,5 - - - -
U
50 to 600 V (phase/phase)
0,2 - - - -
Pst, Plt - - - -
Udip 50 to 600 V
(phase/phase)
0,2 or
0,5
--- -
Uswl 50 to 600 V
(phase/phase)
0,2 or
0,5
--- -
Uint
50 to 600 V (phase/phase)
0,5 - - - -
Unba - - - - -
Unb - - - - -
Uh
50 to 600 V (phase/phase)
1--- -
Ih 0,1 to 1,2 A for TC 1A
0,5 to 6 A for TC 5A
1--- -