56 EN
DIRIS Digiware D-50 & D-70 - 548088B - SOCOMEC
Annex I - 4. SNMP ports
The DIRIS Digiware D-50 / D-70 is congured with standard SNMP ports to receive requests and send notications:
PORT DESCRIPTION
161 Used to send and receive requests from the manager.
162 Used by the manager to receive notifications from the agent
Manager
U-30
@3
I-30
@4
I-30
@5
D-50/D-70
Digiware bus
Manager Port 161
Port 161 Response
Port 162 Traps
Annex I - 5. Retrieving data using the DIRIS Digiware D-50 / D-70 MIB le
The DIRIS Digiware D-50 / D-70 is compliant with MIB-II dened by the MIB standard RFC 1213 which denes the
following structure:
Root
OID Tree Example
iso (1)
org (3)
dod (6)
Internet (1)
directory (1)
mib-2 (1)
interfaces (2) ip (4)system (1)
mgm (2) experimental (3) private (4)
enterprise (1)
vendor X (2) vendor Y (9) SOCOMEC (4555)
The standard branches are under the same parent branch structure: 1.3.6.1.4.1
The “Private (4)” group enables vendors to dene private branches including the MIB OIDs of their own products.
Data related to SOCOMEC metering devices is located under the SOCOMEC enterprise category identied by OID
1.3.6.1.4.1.4555. This implies that all queries from a manager to SOCOMEC agents will start by the base path
1.3.6.1.4.1.4555.
Because the DIRIS Digiware is a multi-circuit system, the DIRIS Digiware D-50 / D-70 creates a dynamic table which
depends on the products connected downstream compatible with the DIRIS Digiware D-50 / D-70 and the loads
congured on each product.
After adding/deleting a downstream device or a load, make sure to update the topology of the D-70 display. This can be
done either directly from the display or from Webview:
Add or delete a device
Refresh the loads
Example: The OID for “Current Inst I1” will return a value for all I-xx, B-xx, DIRIS A etc.. On the contrary, the OID for “THD
Inst I1” will return “0” for an I-30 or an I-31 module.
This implies that each OID can be associated with several products and several loads.