EasyManua.ls Logo

socomec DIRIS Digiware D-50 - 5 Introduction; Range; Introduction to DIRIS Digiware D; Introduction to DIRIS Digiware

socomec DIRIS Digiware D-50
70 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8 EN
DIRIS Digiware D-50 & D-70 - 548088B - SOCOMEC
5. INTRODUCTION
5.1. Range
DIRIS Digiware D-50
Multipoint display
Ref. 48290204
DIRIS Digiware D-70
Multipoint display
Ref. 48290203
Ethernet output
Modbus TCP
BACnet IP
SNMP v1, v2 & v3
Ethernet output
Modbus TCP
BACnet IP
SNMP v1, v2 & v3
-
WEBVIEW-M embedded
web server Power & Energy
Monitoring
5.2. Introduction to DIRIS Digiware D
DIRIS Digiware D-50 and D-70 are system displays and act as the unique point of access to measurements fromDIRIS
Digiware modules.
They can also display measurements from other SOCOMEC meters and measuring devices: COUNTIS, DIRISA, DIRISB.
They centralise data from up to 32 devices (a maximum of 192 circuits).
These products may be connected by a Digiware bus and/or an RS485 bus.
Centralised products can be shown as well as congured by DIRIS Digiware D displays.
5.2.1. Introduction to DIRISDigiware D-50
The DIRIS Digiware D-50 display is a master on the Digiware bus and acts as a gateway interface to communicate
measurements over RS485 and Ethernet.
The RS485 port can be congured as a Master or Slave.
The Ethernet port is used to:
Communicate via Modbus TCP (max. 16 simultaneous connections), measurements from meters and measuring
devices connected to the Digiware and RS485 buses.
Communicate via BACnet IP and SNMP, measurements from meters and measuring devices connected to the
Digiware and RS485 buses.
Automatically send alarm notications via emails (SMTPS).
Synchronize the date/time to an SNTP server.
Automatically and cyclically export historical measurements via FTPS.

Table of Contents