MASTERYS BC+ 10-40 kVA - Ref.: IOMMASBCXX0G-EN 00
6.2 UPS CONNECTION
• Remove terminal board protection.
• Connect the protective earth (PE) cable.
WARNING!
Strictly observe:
- the polarity of each individual string (refer to the figure below);
- the cable cross section (refer to 'Electrical requirements' chapter).
WARNING!
Cabling errors with inversion between phase and neutral conductors may cause permanent
damage to the equipment.
Reassemble terminal board protection.
UPS In/Out
phase
Battery
type
Details
1
kVA
10-15-20 3/1 Internal
battery
3/3
Common
inputs
30-40 3/3
Separated
inputs
1. For further details refer to 'Electrical requirements' chapter.