EasyManua.ls Logo

socomec MASTERYS BC+ 30kVA - Kit for Tn-C; Neutral-Ground Connection; Ramp for Ups Unloading

socomec MASTERYS BC+ 30kVA
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
48 EN
MASTERYS BC+ 10-40 kVA - Ref.: IOMMASBCXX0G-EN 00
11.12 KIT FOR TN-C / NEUTRAL-GROUND CONNECTION
To deal with different plant needs, a connection bar between Neutral and Protection Earth is available as an option
(see figure). For further information contact SOCOMEC.
The UPS does not ensure continuity of the neutral conductor.
The output neutral must not be used as a PEN connection for the load.
A PEN conductor is prohibited in the case of unbalanced and third harmonic current circulation.
TN-C-S connection TN-C connection
Aux mains
Input mains
PEN
Output
Aux mains
Input mains
PEN
Use the same Neutral PEN section of the power connections.
11.13 RAMP FOR UPS UNLOADING

Table of Contents

Related product manuals