MASTERYS BC+ 10-40 kVA - Ref.: IOMMASBCXX0G-EN 00
9. OPERATING PROCEDURES
NOTE: before carrying out any operations on the unit read the 'Safety standards' chapter care-
fully.
NOTE: with the stop procedure the load will be disconnected.
9.1 SWITCHING ON
Connect the mains and auxiliary mains to the UPS.
• Switch ON input switch Q1.
Wait until display switch on.
Enter MAIN MENU > CONTROLS > PROCEDURE.
Select START PROCEDURE and press ENTER.
Carry out the operations indicated on the display.
9.2 SWITCHING OFF
This operation interrupts the power supply to the load. The UPS and the battery charger will be shut down.
Enter MAIN MENU > CONTROLS > PROCEDURE.
Select STOP PROCEDURE and press ENTER.
Wait approx. 2 minutes for the UPS shutdown.
NOTE: the controlled shutdown of each server connected to the LAN can be managed by shut-
down software.
Carry out the operations indicated on the display.
9.3 BYPASS OPERATIONS
SWITCHING ONTO MAINTENANCE BYPASS
This operation creates a direct connection between the UPS input and output, excluding the equipment control part.
This operation is performed in the event of:
- standard maintenance.
- serious failure has occurred.
WARNING! LOAD POWERED BY AUX MAINS: your load is exposed to mains disturbances.
Enter MAIN MENU > CONTROLS > PROCEDURE.
Select MAINT. BYPASS PROC. and press ENTER.
Carry out the operations indicated on the display.
NOTE!
When an external manual bypass is present:
- carry out the procedure described above;
- put the switch to position 1.