MASTERYS BC+ 10-40 kVA - Ref.: IOMMASBCXX0G-EN 00
11.1 ADC+SL CARD
The ADC+SL (Advanced Dry Contact + Serial Link) is a slot optional board that provides:
• 4 relays for external device activation (can be set as normally closed or normally open).
• 3 free inputs to report external contacts to UPS.
• 1 connector for external battery temperature sensor (optional).
• RS485 insulated serial link providing MODBUS RTU protocol.
• 2 LEDs indicating board status.
The board is plug&play: the UPS is able to recognise its presence and configuration (up to 4 standard operating
modes can be selected by the display) and manages the ADC+SL outputs and the inputs accordingly. It is possible
to create a custom operation mode through after sales service.
A
C
D
B
KEY
A 3 free inputs to link external contacts to UPS. C 1 connector for external temperature sensor.
B 4 relays for external device activation. D RS485 insulated serial link.
NOTE!
If the board is removed while operating, an alarm is flagged on the control panel.
Perform an “Alarm reset” control to cancel it.
INPUT
• Free voltage loop.
• INx+ has to be connected to INx- to close the loop on
A
connector.
• Inputs must be isolated with basic insulation from a primary circuit up to 277 V.
• IN1 is duplicated, giving the possibility to link the UPS POWER OFF signal to other equipment, for example.
RELAY OUTPUTS
• Contact voltage guaranteed at 277 V (AC) / 25 V (DC) – 4 A (for higher voltage, please contact the manufacturer).
• Relay 1 gives the possibility of choosing between normally closed (NC1) or normally open (NO1) position. Relays 2,
3 and 4 only have normally open position (NOx).
• On connector
B
, Cx means common, NOx means normally open position.