MASTERYS BC+ 10-40 kVA - Ref.: IOMMASBCXX0G-EN 00
8.4 MENU FUNCTION DESCRIPTIONS
8.4.1 ENTERING PASSWORDS
Some operations and settings require a password in order to be performed.
Confirm password
Cancel character
The default password is SOCO.
Press UP and DOWN to scroll the letters. Press ENT to confirm the selection or ESC to abort.
8.4.2 ALARMS MENU
This menu displays all pending UPS alarms.
To reset alarms enter the menu MAIN MENU > CONTROLS > MAINTENANCE > ALARMS RESET.
If there is more than one page press UP/DOWN to scroll pages.
8.4.3 STATUS MENU
This menu displays all UPS ON statuses.
If there is more than one page press UP/DOWN to scroll pages.
8.4.4 EVENT LOG MENU
This menu accesses the event log (Status and Alarms).
8.4.5 MEASUREMENTS MENU
This menu displays all UPS measurements relating to the input stage, output stage, batteries and auxiliary mains
(bypass).
If there is more than one page press UP/DOWN to scroll pages.
8.4.6 CONTROLS MENU
This menu contains the controls that can be sent to the UPS. Some of them are password protected. If a command
is not available, a COMMAND FAILURE message appears.
PROCEDURE: START PROCEDURE/MAINT. BYPASS PROC./STOP PROCEDURE see 'Operating procedures'
chapter.
BATTERY: BATTERY TEST: this function checks whether or not test conditions are available then returns the
results.
ECO MODE: ON/OFF: this function sets/resets the ECO MODE.
MAINTENANCE: ALARMS RESET: this function clears the alarm history, LED TEST: this function activates the LED
by flashing for few seconds.
8.4.7 USER PARAMETERS MENU
This menu contains all the machine settings such as language, date and buzzer.
To reset the language back to English, press the ESC button for 5 seconds.
System critical parameters are password protected and should be changed by specialist personnel only.