EasyManua.ls Logo

socomec STATYS - Measurements Tables

socomec STATYS
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
STATYS
Jbus / Modbus serial link
12 OPMSTAJB0810-GB_01
ITALIANOENGLISH
8. 5. meaSurementS tableS: StartIng addreSS 0x0220, 64 wordS
CODE DESCRIPTION Unit ADDRESS Remarks
M00 S1 voltage L1N
V
0x0220
M01 S1 voltage L2N
V
0x0221
M02 S1 voltage L3N
V
0x0222
M03 S1 voltage U12
V
0x0223
M04 S1 voltage U23
V
0x0224
M05 S1 voltage U31
V
0x0225
M06 S1 frequency
Hz
0x0226
M07 SS1 temperature
°C
0x0227
M08 S2 voltage L1
V
0x0228
M09 S2 voltage L2
V
0x0229
M10 S2 voltage L3
V
0x022A
M11 S2 voltage U12
V
0x022B
M12 S2 voltage U23
V
0x022C
M13 S2 voltage U31
V
0x022D
M14 S2 frequency
Hz
0x022E
M15 SS2 temperature
°C
0x022F
M16 Output voltage L1
V
0x0230
M17 Output voltage L2
V
0x0231
M18 Output voltage L3
V
0x0232
M19 Output voltage U12
V
0x0233
M20 Output voltage U23
V
0x0234
M21 Output voltage U31
V
0x0235
M22 Output frequency
Hz
0x0236
M23 0x0237
M24 Output current I1
A
0x0238
M25 Output current I2
A
0x0239
M26 Output current I3
A
0x023A
M27 Output current IN
A
0x023B
M28 0x023C
M29 Output load rate
%
0x023D
M30 0x023E
M31 S1-S2 phase shift
°
0x023F
M32 Output Apparent P. L1
KVA
0x0240