Jbus / Modbus serial link
14 OPMSTAJB0810-GB_01
ITALIANOENGLISH
8. 6. permISSIonS tableS: StartIng addreSS 0x0150, 1 wordS
CODE DESCRIPTION BIT ADDRESS Remarks
P00 Close SSP 0 0x0150
P01 Close SSA 1 0x0150
P02 Close SS1 2 0x0150
P03 Close SS2 3 0x0150
P04 S1 is preferred source 4 0x0150
P05 S2 is preferred source 5 0x0150
P06 6 0x0150
P07 Lock transfer ext. 7 0x0150
P08 Unlock transfer ext. 8 0x0150
P09 9 0x0150
P10 Allows remote controls 10 0x0150
P11 Forbid remote controls 11 0x0150
P12 Trsf Asynchro Forced 12 0x0150
P13 Trsf OnFly Abort 13 0x0150
P14 14 0x0150
P15 Load o 15 0x0150
8. 7. commandS tableS: StartIng addreSS 0x0190, wrIte 1 wordS
To modify a parameter, write 1 in the corresponding bit.
CODE DESCRIPTION BIT to write ADDRESS Remarks
C00 Close SSP 0 0x0190
C01 Close SSA 1 0x0190
C02 Close SS1 2 0x0190
C03 Close SS2 3 0x0190
C04 S1 is preferred source 4 0x0190
C05 S2 is preferred source 5 0x0190
C06 6 0x0190
C07 Lock transfer ext. 7 0x0190
C08 Unlock transfer ext. 8 0x0190
C09 9 0x0190
C10 Allows remote controls 10 0x0190
C11 Forbid remote controls 11 0x0190
C12 Force Asynchro Trsf 12 0x0190
C13 Abort OnFly Trsf 13 0x0190
C14 14 0x0190
C15 Load o 15 0x0190
It is advised to modify only one parameter per request.