Shenzhen SOFARSOLAR Co., Ltd.
Energy storage integrated inverter
Product Model: HYD 5K~20KTL-3PH
User manual

Questions and Answers

  • K
    Karen MillerSep 15, 2025
    What to do if Sofar solar HYD 6KTL-3PH Inverter AC frequency is too high?
    • T
      Timothy ReedSep 15, 2025
      If the AC frequency of your Sofar solar Inverter is too high, please ensure the grid frequency and voltage are within the acceptable range.
  • R
    Robert DunlapAug 25, 2025
    What to do if Sofar solar HYD 6KTL-3PH displays GFCI error?
    • T
      Tara OrtizAug 25, 2025
      If your Sofar solar inverter displays a GFCI error, switch OFF the inverter, wait for 5 minutes, and then switch it ON again to see if the problem is resolved. If the error persists, it may indicate internal faults of the inverter, and you should contact technical support for further assistance.
  • R
    Raymond MercerAug 25, 2025
    What to do if Sofar solar HYD 6KTL-3PH Inverter displays TempFault_Bat error?
    • E
      Elizabeth KingAug 26, 2025
      If your Sofar solar inverter displays a TempFault_Bat error, ensure that the battery NTC cable is properly connected for Inner BMS battery. Also, make sure the inverter is installed where there is no direct sunlight, in a cool and well-ventilated place. Ensure the inverter is installed vertically and the ambient temperature is below the inverter temperature limit.
  • M
    Megan AllenAug 26, 2025
    Why Sofar solar Inverter shows OverTempDerating?
    • W
      William AndradeAug 27, 2025
      The OverTempDerating error on your Sofar solar inverter indicates it's overheating. To resolve this, ensure the inverter is installed in a cool, well-ventilated area away from direct sunlight. Also, verify that the inverter is mounted vertically and that the ambient temperature is below the inverter's temperature limit.
  • T
    Tabitha GarciaSep 16, 2025
    What to do if Sofar solar HYD 6KTL-3PH Inverter displays 'Battery low voltage protection'?
    • T
      Theresa JacksonSep 17, 2025
      If your Sofar solar Inverter shows a 'Battery low voltage protection' message, check whether the battery voltage of the inverter is too low.
  • N
    nmooreSep 23, 2025
    What to do if Sofar solar HYD 6KTL-3PH displays 'Master does not exist or is duplicate'?
    • B
      Brian JonesSep 23, 2025
      If your Sofar solar Inverter shows 'Master does not exist or is duplicate', check the parallel mode settings for the inverter and ensure the wiring is correct.
  • Q
    qesparzaSep 8, 2025
    How to fix PvConfigError on Sofar solar HYD 6KTL-3PH?
    • A
      Adam GarciaSep 8, 2025
      To fix a PvConfigError on your Sofar solar Inverter, check the PV input mode (parallel/independent mode) settings for the inverter and change the PV input mode if needed.
  • T
    Todd JohnsonSep 9, 2025
    What to do if Sofar solar HYD 6KTL-3PH shows grid overvoltage?
    • O
      orteganancySep 9, 2025
      If your Sofar solar Inverter is showing a grid overvoltage error occasionally, it might be due to temporary grid issues; the inverter should return to normal when the grid stabilizes. However, if this happens frequently, verify that the grid voltage/frequency is within the acceptable range. If it is, inspect the AC circuit breaker and AC wiring of the inverter. If the grid voltage/frequency is outside the acceptable range and the AC wiring is correct, and the alarm persists, you may need to contact technical support to adjust the grid over-voltage, under-voltage, over-frequency, under-frequency protection points, but only after getting approval from your local electrical grid operator.
  • S
    sabrinagarciaSep 2, 2025
    Why does my Sofar solar HYD 6KTL-3PH Inverter show a BMSCommunicationFault?
    • D
      Daniel TranSep 2, 2025
      A BMSCommunicationFault on your Sofar solar inverter may occur if your battery is not compatible with the inverter. CAN communication is recommended. Check the communication line or port of the battery and inverter for faults.
  • W
    walkerstephanieAug 31, 2025
    What causes PVOVP error on Sofar solar Inverter and how to fix it?
    • A
      Abigail CastilloAug 31, 2025
      The PVOVP error on your Sofar solar inverter indicates that the PV series voltage (Voc) is higher than the maximum input voltage of the inverter. To resolve this, check whether the PV series voltage is indeed too high. If it is, adjust the number of PV modules in series to reduce the PV series voltage, ensuring it fits within the input voltage range of the inverter. After making this correction, the inverter should automatically return to its normal state.

Summary

Basic Safety Information

Safety Instructions

Details essential safety precautions and guidelines for operating the inverter.

Qualified Persons

Specifies requirements for personnel authorized to install and maintain the inverter.

Product Characteristics

Installation

Installation Process

Provides a step-by-step guide for the inverter installation procedure.

Electrical Connections

Battery Connection & PV Connection

Details how to connect the battery and PV modules to the inverter.

AC Load Connection

Guides on connecting the AC load to the inverter.

AC Grid Connection

Explains how to connect the inverter to the AC grid.

Communication Method

Operation (Commissioning)

Double Check

Lists checks to perform before operating or commissioning the inverter.

First Time Setup (IMPORTANT!)

Provides critical steps for the initial setup and power-on procedure.

Wiring, Installation and Setup of Inverter Matching AMASSTORE GTX3000 Battery Packs

Only One Battery Pack Connected

Details wiring and configuration for a single battery pack connection.

Troubleshooting

Technical Data

Quality Assurance

Sofar solar HYD 6KTL-3PH Specifications

General IconGeneral
Rated Output Power6000 W
Max. DC Input Power9000 W
Number of MPPTs2
Nominal AC Output Power6000 W
Max. AC Output Power6600 VA
Nominal Grid Frequency50 Hz / 60 Hz
THDI<3%
Max Efficiency98.4%
DC SwitchYes
Protection DegreeIP65
Operating Temperature Range-25°C to +60°C
CoolingNatural Convection
Nominal AC Voltage230V / 400V
AC Voltage Range310 V - 480 V
Power Factor0.8 leading to 0.8 lagging
CommunicationRS485, Wi-Fi