What to do if Sofar solar HYD 6KTL-3PH shows Grid OVP?
- JJacqueline BanksAug 23, 2025
If the Grid OVP alarm occurs occasionally, the inverter will automatically return to normal operation when the electric grid returns to normal. However, if the alarm occurs frequently, verify that the grid voltage/frequency is within the acceptable range. If it is, inspect the AC circuit breaker and AC wiring of the inverter. If the grid voltage/frequency is outside the acceptable range and the AC wiring is correct, but the alarm persists, contact technical support to adjust the grid over-voltage, under-voltage, over-frequency, and under-frequency protection points after getting approval from the local electrical grid operator. The possible cause is that the electric grid is abnormal occasionally.