Figure 4-9 AC cable connection instruction diagram (1)
Step 3: After assembling the PG waterproof connector, connect the cable to the
AC terminal block L1, L2, L3, N, PE contacts, and fasten them (1~1.6 N · m).
Tighten the lock nut of PG terminal clockwise (5~5.5 N · m).
Figure 4-10 AC cable connection instruction diagram (2)
4.4. Connect PV side of inverter (DC-Input)
Table 4.2 Recommend DC input cable size (maximum tolerance voltage >=
1100V PV cable)
Copper cable cross section area(mm
2
)
Step 1:
Figure 5-2 Recommend DC cable size
Step1: Find the metal contact pins in the accessories bag, connect the cable
according below diagram (1.Positive cable, 2. negative cable)
;