SOFAR 3.3~12KTLX-G3 User manual
Copyright © Shenzhen SOFARSOLAR Co., Ltd.
The power grid
frequency is too high
If the grid voltage/frequency is within the
acceptable range and AC wiring is correct, while
the alarm occurs repeatedly, contact technical
support to change the grid over-voltage,
under-voltage, over frequency, under-frequency
protection points after obtaining approval from
the local electrical grid operator.
The power grid frequency
is too low
If the fault occurs occasionally, the possible cause
is that the external circuits are abnormal
occasionally. inverter automatically returns to
normal operating status after the fault is rectified.
If the fault occurs frequently and lasts a long time,
check whether the insulation resistance between
the PV array and earth(ground) is too low, then
check the insulation conditions of PV cable.
There are internal faults of inverter, turn OFF the
“DC switch”, wait for 5 minutes, then turn ON the
“DC switch”. Check whether the fault is rectified. If
no, please contact technical support.
Grid instantaneous
voltage too high 1
Grid instantaneous
voltage too high 2
The grid current sampling
error
Grid voltage sampling
faulty(DC side)
Grid voltage sampling
faulty(AC side)
Current leakage sampling
(DC side)
There are internal faults of inverter, turn OFF the
“DC switch”, wait for 5 minutes, then turn ON the
“DC switch”. Check whether the fault is rectified. If
no, please contact technical support.
Current leakage sampling
(AC side)
Current Branch sampling
faulty